Switches and Power Points in Wet Areas

There are specific rules when it comes to switches and power points in wet areas. These rules are set out by the AS/NZ 3000 Electrical Wiring Rules.

 

Legislation Information

6.2.4.3 Switches and other accessories

Switches and other accessories shall not be installed within 0.3m of the floor of a bathroom, laundry or other similar location where the floor is likely to become wet.

The following requirements apply to the installation of switches and other accessories in classified zones:

  1. Zone 0 - Switches and other accessories shall not be installed in Zone 0.
  2. Zone 1 and Zone 2 - Only switches and accessories with at least the required degree of protection shall be installed in Zones 1 and 2.

 

Fig-6.13.pngFig-6.14.png